Poor / Damaged Insulation - Thermal Imaging Survey Examples

Poor Insulation at a Large UK Manufacturing Companies

Poor Insulation Heat Loss

Steam pipe work with missing insulation.

Poor Insulation Heat Loss

Heat loss through an un-insulated steam mains pipe.

The energy loss for this pipe was 7kW/m and was wasting £10,811 in fuel/year.

Poor Insulation Heat Loss

External pipe work with missing insulation.

Poor Insulation Heat Loss

Thermal Image showing pipe temperature 87°C, Wind Speed 6mph

Cost of Insulation / Repair £255

Payback Period Only 7 Months

Poor Insulation Heat Loss

Support bracket breaking through insulation

Poor Insulation Heat Loss

Thermal Image showing bracket temperature 121°C, Wind Speed 6mph

Cost of Insulation / Repair £315

Payback Period 15 Months

Impacts from a burns related accident ?


Missing Insulation at a Large UK Manufacturing Company

Poor Insulation Heat Loss

Missing Insulation on a Flange Joint

Poor Insulation Heat Loss

Thermal Image showing flange temperature 172°C, Wind Speed 6mph

Cost of Insulation / Repair £740

Payback Period 13 Months

Impacts from a burns related accident ?


Damaged Insulation at a Large UK Manufacturing Company

Poor Insulation Heat Loss

Damaged Insulation on pipe run (3.5mtrs)

Poor Insulation Heat Loss

Thermal Image showing pipe temperature 64°C, Wind Speed 6mph

Cost of Insulation / Repair £540

Payback Period 21 Months

Impacts from a burns related accident ?